Exciter Model: EXAC8B
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tr < 0.25*Mult*TimeStep then Tr = 0.0
ElseIf 0.25*Mult*TimeStep < Tr < 0.5*Mult*TimeStep then Tr = 0.5*Mult*TimeStep - If 0.0 < Ta < 0.5*Mult*TimeStep then Ta = 0, ElseIf 0.5*Mult*TimeStep < Ta < Mult*TimeStep then Ta = Mult*TimeStep
- If 0 < Te < Mult*TimeStep then Te = Mult*TimeStep
- If 0.0 < Tvd < 0.5*Mult*TimeStep then Tvd = 0, ElseIf 0.5*Mult*TimeStep < Tvd < Mult*TimeStep then Tvd = Mult*TimeStep
- If Vrmax < Vrmin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Vr > Vrmax, then Vrmax = Vr or if Vr < Vrmin, then Vrmin = Vr
Model Equations and/or Block Diagrams
Parameters:
| Tr | Filter time constant, sec |
| Kvp | Voltage regulator proportional gain |
| Kvi | Voltage regulator integral gain |
| Kvd | Voltage regulator derivative gain |
| Tvd | Voltage regulator derivative time constant, sec |
| ViMax | Maximum error, pu |
| Ta | Voltage regulator time constant, sec |
| Vrmax | Maximum exciter control signal, pu |
| Vrmin | Minimum exciter control signal, pu |
| Ke | Exciter field resistance constant, pu |
| Te | Exciter field time constant, sec |
| Kc | Rectifier loading factor proportional to commutating reactance |
| Kd | Exciter internal reactance, pu |
| E1 | Field voltage value, 1 |
| SE1 | Saturation factor at E1 |
| E2 | Field voltage value, 2 |
| SE2 | Saturation factor at E2 |
| Limflg | Limit flag |